Ship with Studio 5000 Logix Designer version 30.00.00 are not compatible with RSNetWorx versionĩ.00.00 or earlier. RSNetWorx and the DeviceNet Tag Generator must be upgraded to a version later After you set up an OPC topic in RSLinx Classic and connect to an OPC client, the values in the Item Properties dialog box are incorrect.Than 9.00.00 prior to installing these products. First identified in RSLinx Classic version 3.80.00. For a controller that supports Ethernet/IP mode switching (for example, 5069-元20ER and 5069-元10ER), after you switch the controller’s IP mode from A1/A2: Dual-IP to A1/A2: Linear/DLR, the two Ethernet networks are merged without an warning message.In this release, after the same operations on RSLinx Classic, the values in the Item Properties dialog box shows correctly. First identified in RSLinx Classic version 3.81.00. When changing the IP address on a module, if the IP changes fail to be saved and the TCP/IP connection is reset (RST), RSLinx Classic does not show an error messages upon this IP change failure.In this release, a warning message is added to indicate the networks merging. First identified in RSLinx Classic version 3.74.00.